Abstract

Globally, buildings are responsible for around 34% of global energy demand, and this consumption is expected to rise with population growth and urbanisation. As a result, there is a pressing need to develop energy-efficient retrofit systems for existing buildings, particularly in developing nations like Indonesia. This study aimed to identify the best energy retrofit solutions for an office building in a hot-humid climate region, using a multi-objective optimisation framework. The optimisation was based on environmental criteria (minimising energy consumption and operational carbon) and social factors (reducing discomfort hours). Key variables in the analysis included the HVAC system, window-to-wall ratio, glazing type, and window blind type. The case study used an eight-storey Indonesian office building built in the 1980s. The current building’s performance was simulated utilising the dynamic thermal modelling software, DesignBuilder (DB), which was successfully calibrated against on-site measured data. The calibrated model was simulated to assess the effectiveness of various retrofit strategies with an optimisation feature available in DB. The optimisation results in 69 sets of optimal retrofit design solutions, which are ranked using a Multi-Criteria Decision-Making (MCDM) framework with the Weighted Sum Model (WSM). The decision-making for optimum solutions was selected based on four priorities, which are energy efficiency, environmental impact, thermal comfort, and the win-win solution. The win-win solution recommends using a cooling setpoint temperature of 26⁰C, using a clear double low-e glass (e2=.1) 6mm/13mm with air cavity, blinds with high reflectivity slats, and an HVAC type of FCU with DOAS with an air-cooled chiller.

Item Type: Conference Item (Unspecified)
Uncontrolled Keywords: multi-objective optimisation, optimum solution, building retrofit, energy efficiency, hot-humid climate
Divisions: Faculty of Humanities & Social Sciences
Faculty of Humanities & Social Sciences > School of the Arts
Depositing User: Symplectic Admin
Date Deposited: 10 Jul 2025 08:02
Last Modified: 07 Nov 2025 07:51
DOI: 10.17866/6xrn-cx50
Related Websites:
URI: https://livrepository.liverpool.ac.uk/id/eprint/3193657
Disclaimer: The University of Liverpool is not responsible for content contained on other websites from links within repository metadata. Please contact us if you notice anything that appears incorrect or inappropriate.